The primary goal of a fire suppression system is to prevent a fire from spreading. This slow-motion video shows a Nero Industry direct release system detecting and suppressing a fire that ignited in an electrical server rack. Here’s what you’re watching.
Fires begin for various reasons in different environments. Combustible liquids, such as the oil-based coolants used in CNC machines, may spark due to friction and ignite. In electrical panels or server racks such as the one in this video, electrical arcing can flash and ignite fires. This causes damage to the equipment by melting wires and igniting other flammable materials in the environment.
An automatic fire suppression system with detection that does not require electricity is protecting the server rack. Routed throughout the server, the red Nero Detection Tubing is a linear, pneumatic heat detector. The system does not require any electricity. If a fire originates within the server rack, the tubing will respond by rupturing and activating the fire suppression system. Watch the tubing begin to warp in response to the fire, ultimately bursting due to the heat.
When the detection tubing reaches a critical temperature, it bursts releasing the pressure of the system. As a direct release system, the fire-suppressing agent discharges through the burst hole in the detection tubing. You can see the tubing recoil with the force of the discharge.
The agent quickly discharges where the fire began, and before it had a chance to spread to cause extensive damage to the equipment. The systems use a clean agent to suppress the fire, which did not damage the electrical equipment.
The detection tubing connects to a pressurized cylinder mounted to the side of the server rack. When the tubing bursts, the pressure differential causes the agent to discharge from the cylinder suppressing the fire. In this video, the direct release system discharges the agent through the burst hole in the detection tubing. Another fire suppression option is an indirect release system. This system is similar except when the fire detection tubing bursts, the change in pressure releases the agent through separate hoses and nozzles.
We saw the system was able to detect and suppress the fire in 10 seconds, discharging enough agent to prevent a reflash from occurring. Regardless of the method of fire suppression, direct and indirect systems protect assets through the detection tubing routed within the enclosure. Understanding fire suppression systems and their capabilities will help you select a system that will mitigate and prevent potential damage to critical assets during a fire.
* Bu sitenin tüm içeriği; metin, grafik, logo, resim, fotoğraf, resim, teknik ve bilimsel çizimler, ses-video klipler, animasyon ve video kayıtları, programlar, bunlarla sınırlı olmamak üzere her türlü teknik unsur ve bunlara ilişkin her türlü haklar dahil olmak üzere, halen yürürlükte olan ve ileride yürürlüğe girecek olan Türkiye Cumhuriyeti Mevzuatı, Site ve içeriği ile doğrudan veya dolaylı olarak ilgili tüm Uluslararası Mevzuatlar tarafından korunmaktadır. NERO Endüstri Savunma Sanayi A.Ş.'nin yazılı izni olmaksızın yukarıda belirtilen unsurların kullanılması, alıntı yapılması, kopyalanması, çoğaltılması, dağıtılması, başka bir bilgisayara yüklenmesi, iletilmesi, değiştirilmesi, ticari amaçla elde tutulması kısmen veya tamamen, doğrudan veya dolaylı olarak, aynen veya değiştirilerek yasaktır. .Ş., söz konusu faaliyetleri teşvik etmek; bunlarla sınırlı olmayan ve bunlarla ilgili her türlü haksız fiil de yasaktır.